Operational Safety

IPTF commenced its commercial operation from March 1st 2015.

  • All Operation and Maintenance related activities are carried out as per defined and established norms. Various SOPs & SMPs are well defined and implemented with provisions for improvement and updation as and when required.
  • We have qualified & experienced O&M Staff operating round the clock. All O&M Staff are trained on the O&M Philosophy and are certified on Basic Firefighting and Basic First Aid.
  • Emergency Response Plan is prepared and training is imparted to all O & M staff.
  • We are certified with latest Integrated Management System (IMS) for ISO 9001:2015 for Quality, ISO 14001: 2015 Environment Protection and OHSAS 18001: 2007 for Operational Safety.

HSSE POLICY

HSSE COMMITMENT

  • IL&FS is committed for the safe and sustainable Operation.
  • We believe that all incidents can be prevented. We strive continuously for zero harm to personal, environment and assets.
  • We conserve the natural resources, protect the environment and provides safe and healthy environment for our employees, visitors and contractual staff.
  • With Focus on employee’s health, we continuously improves the work environment.
  • We do our operations through efficient use of materials and energy, with minimum waste and damage to the environment.

HSSE POLICY

The latest edition of NFPA codes and standards are considered in preparation of fire protection and detection Facilities.

NFPA 10 Standard for Portable Fire Extinguishers
NFPA 11 Standard for Low, Medium and High Expansion Foam
NFPA 12 Standard for Carbon Dioxide Extinguishing Systems
NFPA 13 Standard for Installation of Sprinkler Systems
NFPA 14 Standards for Installation of Standpipe and Hose Systems
NFPA 15 Standard for the Installation of Water Spray Fixed system for Fire Protection
NFPA 16 Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems
NFPA 20 Standard for Installation of Stationary Pumps for Fire Protection
NFPA 22 Water Tanks for Private Fire Protection
NFPA 24 Installation of Private Fire Service Mains and their Appurtenances
NFPA 30 Flammable and Combustible Liquids Code
NFPA 70 National Electric Code
NFPA 72 National Fire Alarm Code
NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems
BS 5839 Part 1 :1980 The Installation and Servicing of Electrical Fire Alarm Systems
UAE Fire and Life Safety Code of Practice – 2011

Fire Fighting Facilities

 Fire Pump House

  • 3 nos. Diesel Operated Fire Water Pumps installed each with the capacity of 1,000 m3/ hr. at 10 bar discharge pressure. Out of these three, two pumps are in service to meet total fire water demand and one pump stand in conformation to NFPA 20.
  • 1 no Electrical Jockey pump of 300 M3/ hr. capacity to maintain fire water header pressure of 10 bar.
  • The Fire water tank (FTK-01) is a fixed roof, Cone type, Atmospheric tank of carbon steel. The basic parameters of this tank is as follows :-
  • Diameter: 20 m; Height: 15 m; Capacity: 4100 m3
  • Fire water tank is always kept full with fresh water.
  • In the worst case scenario (full Surface fire on the largest tank 101), 2 nos. fire water pumps of 1,022 m3/hr. will operate to meet the total fire water demand.
  • Capacity of fire water tank is so designed to provide continuous firefighting operation for 2 hrs.

Fire Hydrants

  • Fire water Hydrants are provided all along the periphery of the Tank farm at 60 m c/c. The fire water lines remains charged with 7 bar pressure.

Fire Hose Cabinets

  • FHC are installed at regular intervals near each fire hydrant which is equipped with
  • 2 Nos. of 30 meter, 2.5” dia. quick coupling Fire hoses
  • 2 Nos. Jet/ Spray nozzles and
  • 1 No of Foam Branch pipe

ESD – Emergency Shut down

  • An Emergency Shut down (ESD) system is provided near each facility. In case of any Emergency like fire or tank leakage, the authorized person shall activate the ESD which shall close all the MOVs of tanks and trip the motors of all the rotary items and packages.

MCP

  • Safety Showers with Eye wash station, are installed in the Terminal at noticeable locations near loading bay, Tank Farm, Pump manifold and PLR (Pig Launcher & Receiver).

Safety Shower

  • Manual Call Points and sounders are installed around Tank farm (Outside Bund wall), Manifold, Truck Loading bay, Utility area, VFD area, Substation, Heating System. These MCP & sounder are connected to Central Fire Alarm Control Panel.